首页 | 本学科首页   官方微博 | 高级检索  
     

机场塔台无高位消防水箱之增强措施探讨
引用本文:衣兰凯,赵乐乐,叶超,连震雷,朱其原. 机场塔台无高位消防水箱之增强措施探讨[J]. 消防科学与技术, 2020, 39(1): 79-80
作者姓名:衣兰凯  赵乐乐  叶超  连震雷  朱其原
作者单位:1. 民航机场规划设计研究总院有限公司,北京100101;2. 国家消防工程技术研究中心,天津300382
摘    要:机场塔台顶层指挥明室因空管工艺需求,屋顶采用轻钢结构,受结构承载力和限高的要求,塔台无法设置高位消防水箱。通过火灾场景、烟气流动模拟和人员安全疏散分析,提出消防强化措施,主要包括采用稳高压消防系统、两路供水、两路供电、采用快速响应喷头、优化管材选择、采用物联网消防设备和配置空气呼吸机等。模拟结果显示,在发生火灾区域的自动灭火系统和排烟系统有效的情况下,清晰高度处的人员可用疏散时间较长,该消防方案能达到防止火灾大规模蔓延和保障建筑内人员安全的消防设计安全目标。

关 键 词:机场塔台  高位消防水箱  安全疏散  稳高压系统  自动灭火系统  
收稿时间:2019-08-25

Discussion about strengthening measures for an airport tower without elevated fire tank
YI Lan-kai,ZHAO Le-le,YE Chao,LIAN Zhen-lei,ZHU Qi-yuan. Discussion about strengthening measures for an airport tower without elevated fire tank[J]. Fire Science and Technology, 2020, 39(1): 79-80
Authors:YI Lan-kai  ZHAO Le-le  YE Chao  LIAN Zhen-lei  ZHU Qi-yuan
Affiliation:1. China Airport Planning & Design Institute Co.,Ltd.,Beijing 100101,China;2. National Center for Fire Engineering Technology, Tianjin 300382,China
Abstract:Due to the requirements of the tower command dim room, the roof adopts light steel structure. The tower cannot set elevated fire tank restricted by bearing capacity of structure and building height. Analyzing fire scene, fire smoke flow and personnel safe evacuation, strengthening measures were proposed, such as fire water supply system of stable-high pressure, two way of water supply,dual power supply, using fast response sprinkler optimizing the selection of pipes, firefighting equipment with internet of things, and deploying air ventilator. Evacuation time was long in the event that the automatic fire extinguishing system and smoke exhaust system in the fire area were effective, achieving the design safety goal which can prevent fire from spreading in large scale and guarantee the personnel safety in the building.
Keywords:airport tower  elevated fire tank  safe evacuation  fire water supply system of stable-high pressure  automatic fire distinguish system