首页 | 本学科首页   官方微博 | 高级检索  
     

火源及通风对地下综合管廊火灾的影响
引用本文:安伟光,王涛,朱国庆,胡凯扬. 火源及通风对地下综合管廊火灾的影响[J]. 消防科学与技术, 2020, 39(3): 331-334
作者姓名:安伟光  王涛  朱国庆  胡凯扬
作者单位:1.中国矿业大学安全工程学院,江苏徐州 221116; 2.中国矿业大学江苏省城市地下空间火灾防护高校重点实验室,江苏 徐州 221116
基金项目:国家自然科学基金项目(51974298);国家重点研发计划项目(2016YFC0802900)。
摘    要:利用PyroSim软件建立一段L型综合管廊模型并进行火灾数值模拟,并运用Origin软件对温度进行分析,研究了火源特性(火源位置和火源功率)及通风条件(风速和风向)对管廊烟气蔓延及温度变化的影响。结果表明,当火源位于管廊中部且功率大时,高温且有毒烟气能够在更短的时间内充满整个管廊,火灾危险性大;风速过大会造成大量的烟气在拐角处积聚,排烟的效果不与风速成正比。

关 键 词:城市地下综合管廊  数值模拟  烟气蔓延  温度变化  

Influence of fire source and ventilation on underground pipe gallery fire
AN Wei-guang,WANG Tao,ZHU Guo-qing,HU Kai-yang. Influence of fire source and ventilation on underground pipe gallery fire[J]. Fire Science and Technology, 2020, 39(3): 331-334
Authors:AN Wei-guang  WANG Tao  ZHU Guo-qing  HU Kai-yang
Affiliation:1. School of Safety Engineering,China Universityof Mining and Technology, Jiangsu Xuzhou 221116, China; 2. Jiangsu KeyLaboratory of Fire Safety in Urban Underground Space,China University of Miningand Technology, Jiangsu Xuzhou 221116,China
Abstract:A section of L shape pipe gallery model was established using PyroSim software and fire numerical simulation was carried out.The temperature was analyzed using Origin software.The influence of fire source characteristics(location and power of fire source)and ventilation conditions(wind speed and direction)on smoke spread and temperature change in pipe gallery was studied.The results showed that when the fire source is located in the middle of the corridor and the power is high,high temperature and toxic fumes can fill the entire pipe gallery in a shorter time,the fire risk is higher.Excessive wind speed causes a large amount of smoke to accumulate at the corner,so the smoke exhaust effect is not directly proportional to the wind speed.
Keywords:underground pipe gallery  numerical simulation  smoke spread  temperature change
本文献已被 CNKI 维普 等数据库收录!
点击此处可从《消防科学与技术》浏览原始摘要信息
点击此处可从《消防科学与技术》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号