首页 | 本学科首页   官方微博 | 高级检索  
     

典型特高压换流变压器火灾数值模拟研究
引用本文:张佳庆,李国辉,汪亚龙,黎昌海,尚峰举,陆守香.典型特高压换流变压器火灾数值模拟研究[J].消防科学与技术,2020,39(8):1115-1120.
作者姓名:张佳庆  李国辉  汪亚龙  黎昌海  尚峰举  陆守香
作者单位:1. 国网安徽省电力有限公司电力科学研究院,安徽合肥230601;2. 应急管理部天津消防研究所,天津300381;3. 中国科学技术大学火灾科学国家重点实验室,安徽合肥230027
基金项目:国家电网有限公司科技重大专项“特高压换流站大型换流变压器灭火关键技术研究与应用”(52120518002L)
摘    要:通过文献调研及事故资料分析,阐释了特高压换流变压器的结构特点和事故工况。采用CFD 数值模拟技术,根据典型事故工况的油料状态、边界条件和环境条件等,设计5 个工况,研究典型特高压换流站变压器火灾的发生和发展过程。分析典型变压器火灾的燃烧形式、热释放速率大小及火源周边温度特性等,获得阀厅外壁面温度对阀厅的影响。设计可脱落式Boxin顶板时,应考虑其在火灾过程初期温度上升较慢、温度较低的特点。为创造换流变火源窒息熄灭的有利条件,应保证阀厅封堵及顶部Box-in 降噪板不受破坏,火灾时主动封闭下3 行散热风扇,阻止空气流入;阀厅封堵破坏时,可以将换流变压器正面散热风扇洞口全部封闭,阻止空气进入。

关 键 词:换流变压器  数值模拟  特高压  火灾  

Numerical simulation study on fire of typical UHV converter transformer
ZHANG Jia-qing,LI Guo-hui,WANG Ya-long,LI Chang-hai,SHANG Feng-ju,LU Shou-xiang.Numerical simulation study on fire of typical UHV converter transformer[J].Fire Science and Technology,2020,39(8):1115-1120.
Authors:ZHANG Jia-qing  LI Guo-hui  WANG Ya-long  LI Chang-hai  SHANG Feng-ju  LU Shou-xiang
Affiliation:1.State Grid Anhui Electric Power Research Institute, Anhui Hefei 230601, China; 2.Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China; 3. State Key Laboratory of Fire Science, University of Science and Technology of China, Anhui Hefei 230027, China
Abstract:Based on literature review and analysis of accident data,the structural characteristics and accident conditions of UHV converter transformer were elaborated. By means of CFD numerical simulation, according to the oil states, boundary conditions and environmental conditions of typical accident conditions, the occurrence and development process of transformer fire in typical UHV converter station were studied based on 5 scenarios. The combustion form, heat release rate and temperature around fire source of typical transformer fire were analyzed. The influence of the temperature of the outer wall of the valve chamber on the valve chamber were obtained. The characteristics of slow temperature rise and low temperature in the early stage of fire should be considered during the design of the detachable Box- in roof. In order to create favorable conditions for the extinction of the converter fire source,the sealing of the valve hall and the Box- in noise reduction plate should not be damaged at fire, and the lower 3 rows of cooling fans should be closed actively to prevent air from flowing in. The front cooling fan hole of the converter should be completely closed to prevent air from entering when the valve hall plugging is damaged.
Keywords:converter transformer  numerical simulation  UHV  fire  
本文献已被 CNKI 等数据库收录!
点击此处可从《消防科学与技术》浏览原始摘要信息
点击此处可从《消防科学与技术》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号