首页 | 本学科首页   官方微博 | 高级检索  
     

输电线路二次自动重合闸方案的设计与验证
引用本文:王震宇,孙正伟,王开白,李卫星,刘家庆,王哲浩,晁璞璞,鲍 斌.输电线路二次自动重合闸方案的设计与验证[J].电力系统保护与控制,2021,49(19):115-123.
作者姓名:王震宇  孙正伟  王开白  李卫星  刘家庆  王哲浩  晁璞璞  鲍 斌
作者单位:国家电网有限公司东北分部,辽宁 沈阳 110180;大连理工大学电气工程学院,辽宁 大连 116024;哈尔滨工业大学电气工程学院,黑龙江 哈尔滨 150001
基金项目:国家电网公司科技项目资助(SGDB0000DKJS 2000104)
摘    要:目前220 kV及以上电压等级线路二次重合闸的必要性与可行性研究尚无完善的技术路线,对于二次重合闸成功与否的影响因素缺乏深入研究,仅将其简单地归结为时间延迟的长短是不够合理的。针对这一问题,以东北电网220 kV及以上电压等级输电线路为研究对象,通过其历史故障信息、重合闸动作情况、以及手动强送结果的梳理和分析,论述了输电线路采用二次自动重合闸的必要性。然后,分析了输电线路重合闸成功与否的影响因素,解析了二次重合闸的时序动作过程。最后,设计了二次自动重合闸的重合方式、整定延时和动作逻辑,形成了较完善的二次自动重合闸方案,并进行了仿真验证。结果表明,所提出的二次自动重合闸方案对220kV和500kV电压等级线路具有良好的适应性。

关 键 词:输电线路  故障统计  二次重合闸  方案设计
收稿时间:2020/12/24 0:00:00
修稿时间:2021/3/3 0:00:00

Design and verification of second automatic reclosing scheme for transmission lines
WANG Zhenyu,SUN Zhengwei,WANG Kaibai,LI Weixing,LIU Jiaqing,WANG Zhehao,CHAO Pupu,BAO Bin.Design and verification of second automatic reclosing scheme for transmission lines[J].Power System Protection and Control,2021,49(19):115-123.
Authors:WANG Zhenyu  SUN Zhengwei  WANG Kaibai  LI Weixing  LIU Jiaqing  WANG Zhehao  CHAO Pupu  BAO Bin
Affiliation:1. Northeast Branch of State Grid Corporation of China, Shenyang 110180, China; 2. School of Electrical Engineering, Dalian University of Technology, Dalian 116024, China; 3. School of Electrical Engineering, Harbin Institute of Technology, Harbin 150001, China
Abstract:At present, there is no perfect technical framework for the necessity and feasibility study of secondary reclosing of 220 kV and above transmission lines. There is a lack of in-depth research on influencing factors of the success of secondary reclosing, and it is unreasonable to simply attribute the influencing factor to the length of time delay. This paper takes the 220 kV and above transmission lines of the Northeast Power Grid as the research object. By analyzing historical fault information, reclosing actions and manual reclosing results, the need for the second automatic reclosing of transmission lines is demonstrated. Then factors affecting the success of the reclosing of transmission lines are investigated, and the sequential action process of the second reclosing is analyzed. Finally, a secondary automatic reclosing strategy, including the reclosing method, setting delay and action logic of the secondary automatic reclosing, is proposed. The simulation results show that the proposed secondary automatic reclosing strategy has good adaptability to 220 kV and 500 kV transmission lines. This work is supported by the Science and Technology Project of State Grid Corporation of China (No. SGDB0000DKJS2000104).
Keywords:transmission lines  fault collection  secondary reclosing  optimal design
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统保护与控制》浏览原始摘要信息
点击此处可从《电力系统保护与控制》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号