基于负序电流的主动配电网单相断线故障保护方法
引用本文:王开科,熊小伏,肖 扬,欧阳金鑫. 基于负序电流的主动配电网单相断线故障保护方法[J]. 电力系统保护与控制, 2021, 49(6): 10-18
作者姓名:王开科  熊小伏  肖 扬  欧阳金鑫
作者单位:国网新疆电力有限公司电力科学研究院,新疆 乌鲁木齐 830011;输配电装备及系统安全与新技术国家重点实验室(重庆大学),重庆 400044
基金项目:国家自然科学基金联合基金项目资助(U1866603)
摘    要:随着分布式电源(DG)的接入以及主动配电网(ADN)的迅速发展,网络结构日趋复杂,断线故障频发,严重威胁设备与人身安全,影响电力系统稳定运行.由于受DG和可变拓扑的影响,ADN断线故障的识别面临较大的挑战,现有研究存在一定的空白,因此提出了一种基于负序电流的ADN单相断线故障保护方法.首先解析分析了DG上、下游发生单相...

关 键 词:主动配电网  分布式电源  断线故障  负序电流  中性点电压
收稿时间:2020-05-31
修稿时间:2020-09-08

Single-phase break fault protection method for an active distribution network based on negative sequence current
WANG Kaike,XIONG Xiaofu,XIAO Yang,OUYANG Jinxin. Single-phase break fault protection method for an active distribution network based on negative sequence current[J]. Power System Protection and Control, 2021, 49(6): 10-18
Authors:WANG Kaike  XIONG Xiaofu  XIAO Yang  OUYANG Jinxin
Affiliation:1. Electric Power Research Institute of State Grid Xinjiang Electric Power Co., Ltd., Urumqi 830011, China; 2. State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400044, China
Abstract:With the access of Distributed Generation (DG) and the rapid development of the Active Distribution Network (ADN), network structure is becoming increasingly complex, frequent break faults seriously threaten equipment and personal safety and affect the stable operation of a power system. Because of the influence of DG, ADN break fault identification faces greater challenges, and there is still a gap in existing research. This paper proposes a single-phase break fault protection method for ADN based on negative sequence current. First, the characteristics of sequence currents and neutral voltage in the case of a single-phase break fault occurring in the upstream and downstream of DG are analyzed. The neutral voltage and negative sequence current are used as the protection parameters, and a single-phase break fault protection criterion for ADN with small resistance grounding based on negative sequence current is constructed. Theoretical analysis and simulation results show that the method is not affected by load distribution, fault location and network topology. It has high sensitivity, reliability, applicability and ease of implementation.This work is supported by the Joint Fund of National Natural Science Foundation of China (No. U1866603).
Keywords:active distribution network   distributed generation   break fault   negative sequence current   neutral voltage