首页 | 本学科首页   官方微博 | 高级检索  
     

基于测试信号法的HVDC谐波阻抗扫描方法研究
引用本文:李清,周强,张东辉,毛炽祖. 基于测试信号法的HVDC谐波阻抗扫描方法研究[J]. 电力系统保护与控制, 2021, 49(14): 168-175
作者姓名:李清  周强  张东辉  毛炽祖
作者单位:中国南方电网有限责任公司超高压输电公司检修试验中心,广东广州 510670;清华四川能源互联网研究院,四川成都 610200
基金项目:南方电网公司科技项目资助(CGYKJXM20180485);四川省科技计划项目资助(2019YJ0631)
摘    要:谐波阻抗扫描是高压直流输电(HVDC)中谐波谐振分析、交流或直流滤波器设计等工作的重要手段.采用电路叠加定理说明了适用于HVDC谐波阻抗扫描的测试信号法.基于测试信号法基本原理及其在HVDC应用研究中的进展,提出测试信号法应用于HVDC谐波阻抗扫描的谐波源幅值选择方法和用于减小谐波源初相位影响的改进扫描方法.最后,以C...

关 键 词:高压直流输电  谐波阻抗扫描  测试信号法  谐波源幅值  谐波源初相位
收稿时间:2020-09-24
修稿时间:2020-11-20

high voltage direct current; harmonic impedance scanning; test signal method; amplitude of harmonic source; initial phase of harmonic source
LI Qing,ZHOU Qiang,ZHANG Donghui,MAO Chizu. high voltage direct current; harmonic impedance scanning; test signal method; amplitude of harmonic source; initial phase of harmonic source[J]. Power System Protection and Control, 2021, 49(14): 168-175
Authors:LI Qing  ZHOU Qiang  ZHANG Donghui  MAO Chizu
Affiliation:1. EHV Maintenance & Test Center, China Southern Power Grid Company Limited, Guangzhou 510670, China; 2. Sichuan Energy Internet Research Institute, Tsinghua University, Chengdu 610200, China
Abstract:Harmonic impedance scanning is an important means of harmonic resonance analysis and AC or DC filter design in HVDC. In this paper, the circuit superposition theorem is used to explain the test signal method which is suitable for HVDC harmonic impedance scanning. Based on the basic principle of the test signal method and how it has progressed in HVDC application research, a method of selecting harmonic source amplitude and an improved scanning method for reducing the influence of the initial phase of the harmonic source are proposed. Finally, taking the CIGRE first benchmark model as an example, the influence of harmonic source amplitude and initial phase on harmonic impedance scanning is quantitatively and qualitatively analyzed on a PSCAD/EMTDC simulation platform to verify that the proposed method can be used to further improve the reliability of harmonic impedance scanning results of HVDC, and provide a reference for actual HVDC project design.This work is supported by the Science and Technology Project of China Southern Power Grid (No. CGYKJXM20180485) and Sichuan Science and Technology Plan (No. 2019YJ0631).
Keywords:high voltage direct current   harmonic impedance scanning   test signal method   amplitude of harmonic source   initial phase of harmonic source
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统保护与控制》浏览原始摘要信息
点击此处可从《电力系统保护与控制》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏