首页 | 本学科首页   官方微博 | 高级检索  
     


Electricity end-use characteristics of air-cooled chillers in hotels in Hong Kong
Affiliation:1. IDMEC, Instituto Superior Técnico, Universidade de Lisboa, Portugal;2. DEM-ISEP, Instituto Politécnico do Porto, Portugal;3. Departamento de Ingeniería Mecánica y Diseño Industrial, Escuela Superior de Ingeniería, Universidad de Cádiz, Spain
Abstract:This paper presents the operating efficiency of air-cooled chillers in three existing hotels and investigates the extent to which the annual electricity consumption can decrease by improving their efficiency. Chillers in these hotels tend to be improperly staged, causing their seasonal efficiency to rise by 0.05–0.12 kW/kW from a full load efficiency of 0.32 kW/kW. When chiller sequencing is restored, their seasonal efficiency could be enhanced to 0.34 kW/kW, which corresponds to an 8.8–22.7% drop in their annual electricity consumption. It is possible to further decrease the annual electricity consumption by 27.0–38.6% when the chillers operate under floating condensing temperature control instead of head pressure control. The implications of improved chiller efficiency for reducing the electricity demand of hotels are discussed.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号