首页 | 本学科首页   官方微博 | 高级检索  
     

基于分形理论与聚类分析的小电阻接地系统高阻接地保护方法
引用本文:曹文思,吴擎,徐铭铭,牛荣泽. 基于分形理论与聚类分析的小电阻接地系统高阻接地保护方法[J]. 电力自动化设备, 2020, 40(4): 204-209,224
作者姓名:曹文思  吴擎  徐铭铭  牛荣泽
作者单位:华北水利水电大学 电力学院,河南 郑州 450045,华北水利水电大学 电力学院,河南 郑州 450045,国网河南省电力公司电力科学研究院,河南 郑州 450002,国网河南省电力公司电力科学研究院,河南 郑州 450002
基金项目:2019年度河南省重点研发与推广专项(科技攻关)项目(192102210229);河南省高等学校重点科研项目(19A470006);2019年度河南省高等学校青年骨干教师培养计划(2019GGJS104)
摘    要:针对目前小电阻接地系统保护由于整定值过大而对高阻接地故障易出现拒动的问题,基于分形理论和聚类分析提出了高阻接地保护新方法。该方法提取故障线路和非故障线路零序电流的相似性特征,利用零序电流比值和分形维数对相似度进行量化计算,构建了接地故障特征矩阵,采用K-means聚类算法对接地故障特征矩阵进行分析,避免了保护整定困难的问题。经真型实验录波数据验证,所提方法将保护的耐阻能力提高到2000Ω,具有一定的应用价值。

关 键 词:小电阻接地系统  高阻接地  分形理论  相似性  聚类分析  继电保护
收稿时间:2019-03-10
修稿时间:2019-12-20

Protection method based on fractal theory and cluster analysis for grounding fault with high resistance of low resistance grounding system
CAO Wensi,WU Qing,XU Mingming and NIU Rongze. Protection method based on fractal theory and cluster analysis for grounding fault with high resistance of low resistance grounding system[J]. Electric Power Automation Equipment, 2020, 40(4): 204-209,224
Authors:CAO Wensi  WU Qing  XU Mingming  NIU Rongze
Affiliation:School of Electric Power, North China University of Water Resources and Electric Power, Zhengzhou 450045, China,School of Electric Power, North China University of Water Resources and Electric Power, Zhengzhou 450045, China,State Grid Henan Electric Power Research Institute, Zhengzhou 450002, China and State Grid Henan Electric Power Research Institute, Zhengzhou 450002, China
Abstract:Because the setting value of the protection in low resistance grounding system is too large,the protection in low resistance grounding system easily refuses to operate when a high-impedance grounding fault occurs.Aiming at this problem,a novel protection method based on fractal theory and cluster analysis for grounding fault with high resistance of low resistance grounding system is proposed.The similarity cha-racteristics of zero-sequence current between fault line and normal lines are extracted.The characteristic matrix of grounding fault is constructed by the similarity of zero-sequence currents that quantified by ratio of zero-sequence currents and fractal dimension,and analyzed by K-means clustering algorithm.The pro posed method avoids the difficulty of protection setting.The true-mode experimental recording data verify that the high resistance capacity of protection is improved to 2000Ωby the proposed method,which has certain application value.
Keywords:low resistance grounding system   high resistance grounding   fractal theory   similarity   cluster analysis   relay protection
本文献已被 CNKI 维普 等数据库收录!
点击此处可从《电力自动化设备》浏览原始摘要信息
点击此处可从《电力自动化设备》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号