Performance characterization of a small-capacity thermoacoustic cooler for air-conditioning applications |
| |
Authors: | Insu Paek Luc Mongeau James E. Braun |
| |
Affiliation: | (1) Department of Mechanical Engineering, The Johns Hopkins University, 3400 North Charles Street, Baltimore, MD 21218, USA;(2) Institute of Thermomechanics, Academy of Sciences of the Czech Republic, Prague, Czech Republic |
| |
Abstract: | The performance of a working prototype, operated with and without water flow through the heat exchangers, was measured and found to be in reasonably close agreement to predictions from a simulation code, DELTAE, based on linear thermoacoustic theory. Further analysis and DELTAE simulations showed that the coefficient of performance may be significantly reduced when the stack temperature profile becomes non-linear, i.e. when the system is operated for a temperature span smaller than the optimal value for a given stack length. Guidelines to avoid this condition are provided. |
| |
Keywords: | |
本文献已被 SpringerLink 等数据库收录! |
|