首页 | 本学科首页   官方微博 | 高级检索  
     


A method for load frequency control using battery in power system with highly penetrated photovoltaic generation
Authors:Hiroyuki Nagoya  Shintaro Komami  Kazuhiko Ogimoto
Affiliation:1. Hokuriku Electric Power Co., , Japan;2. University of Tokyo, , Japan
Abstract:It is generally believed that large battery systems will be needed to store surplus electric energy due to the high penetration of renewable energy (RE) such as photovoltaic generation (PV). Since the main objective of high penetration of RE is to reduce CO2 emissions, reducing kWh output of thermal generation that emits large amounts of CO2 in power systems should be sufficiently considered. However, thermal generation plays an important role in load frequency control (LFC) of power systems. Therefore, if LFC could be performed with batteries and hydropower generation, the kWh output of thermal generation could be reduced significantly. This paper presents a method of LFC using batteries in a power system with highly penetrated PVs. An assessment of the effect of the proposed method considering mutual smoothing effect of highly penetrated PVs is made. © 2013 Wiley Periodicals, Inc. Electr Eng Jpn, 184(4): 22–31, 2013; Published online in Wiley Online Library ( wileyonlinelibrary.com ). DOI 10.1002/eej.22425
Keywords:battery system  load frequency control  power fluctuation  photovoltaic generation  smoothing effect
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号