首页 | 本学科首页   官方微博 | 高级检索  
     

闭冷水泵节能优化改造
引用本文:刘勇. 闭冷水泵节能优化改造[J]. 电力情报, 2008, 0(7): 25-27
作者姓名:刘勇
作者单位:福建大唐国际宁德发电有限责任公司,福建宁德355006
摘    要:针对大唐宁德发电公司600MW机组闭冷水泵运行中存在的扬程裕量大、调节不合理、电耗高等问题,对水泵进行了节能优化改造。改造后泵的最高运行效率从78.48%提高到了90.37%。改造后平均耗电率下降了40%,节约电功率240kW。改造方案简单,投资少,效益高,适用于所有的大型机组闭冷水泵。

关 键 词:闭冷泵  通流部分  型线改进  经济效益

Energy-conservation Optimization Reconstruction for Circle Cooling Water Heating Exchanging Pump
Liu Yong. Energy-conservation Optimization Reconstruction for Circle Cooling Water Heating Exchanging Pump[J]. Information on Electric Power, 2008, 0(7): 25-27
Authors:Liu Yong
Affiliation:Liu Yong (Fujian Datang International Ningde Power Generation Co., Ltd., Ningde 355006, China)
Abstract:Aiming to the problems existing in the running of 600 MW units circle cooling water heating exchanging pump which is in Datang Ningde Power Generation Co., Ltd., such as large head margin, irrational adjustment, and high power consumption, etc, pump is processed energy-conservation optimization reconstruction. After constructing, its highest running efficiency is improved from 78.48 percent to 90.37 percent. The average power-consumption rate is decreased to 40 percent, and the saves electrical power is 240 kW. The rebuilding scheme, which is simple and low-cost, is adapt to circle cooling water heating exchanging pumps in all kinds of large-scale units.
Keywords:circle cooling water heating exchanging pump  flow passage  outline improvement