首页 | 本学科首页   官方微博 | 高级检索  
     


Fault Location in Neutral Non-effectively Grounded Distribution Systems Using Phase Current and Line-to-line Voltage
Authors:Jinrui Tang  Xianggen Yin  Minghao Wen  Zhe Zhang
Affiliation:State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan, China
Abstract:Abstract—A scheme of single-line-to-ground fault location in neutral non-effectively grounded distribution systems is proposed in this article. The characteristics of phase current traveling waves and line-to-line voltage traveling waves are analyzed. The wavelet transform technique is used to extract the information of the arrival times, polarities, and amplitudes of the recorded traveling waves. The fault location scheme can simultaneously realize faulty feeder identification, fault section location, and fault position location even if only two-phase current transformers are installed in the Phases A and C and feeder terminal units only to provide line-to-line voltage information. The effectiveness and practicability of the proposed scheme have been verified by PSCAD/EMTDC simulation results.
Keywords:distribution systems  fault location  non-effectively grounding  traveling wave