首页 | 本学科首页   官方微博 | 高级检索  
     


A New Rate of Change of Impedance-based Islanding Detection Scheme in Presence of Distributed Generation
Authors:Pragnesh H Shah
Affiliation:Department of Electrical Engineering, A. D. Patel Institute of Technology, New Vallabh Vidhyanagar, Gujarat, India
Abstract:Abstract—Integration of distributed generation with utility network demands satisfactory operation of an islanding detection scheme, as it can otherwise lead to such problems such enhancement in non-detection zone, out-of-phase reclosing, personnel safety, and degradation of power quality. This article presents a new islanding detection scheme based on the rate of change of impedance (dz/dt) of each phase. To calculate dz/dt, phasor computation is carried out using a half-cycle modified discrete Fourier transform algorithm. Test data are generated using the PSCAD/EMTDC software package (HVDC Research Center, Inc., Manitoba). Various islanding conditions have been simulated by disconnecting the main circuit breaker with different values of active and reactive power mismatch. At the same time, different non-islanding conditions have also been simulated through switching (ON/OFF) of load, energization/de-energization of medium transmission lines, short-circuit on an adjacent feeder, and switching (ON/OFF) of the transformer and capacitor bank in the network. The simulation results indicate that the proposed scheme is capable of providing effective discrimination between islanding and non-islanding conditions. The proposed scheme is able to detect islanding conditions within a half-cycle from event inception.
Keywords:distributed generation  islanding detection  rate of change of impedance relay  non-islanding conditions
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号