Ozone Treatment in Cooling Water Systems
Authors:N. Kaiga  T. Seki  K. Iyasu
Abstract:Ozone treatment for preventing the biofouling in cooling water systems is investigated.

In the fresh water system, the separating effect of the ozonated water on the microorganisms such as the sphaerotilus and the zoogloea which adhere to the piping and form the slime is recognized. When the ozonated water is supplied intermittently to the piping without stopping the flow of the cooling water, a constant volume of cooling water can be maintained. At the velocity of 1 m/sec, the amount of metal corrosion produced by the ozonated water is reduced on the mild steel, increased on the copper and does not change on the cast iron, when compared with that produced by the water containing no ozone.

In the seawater system, since many substances are oxidized by the ozone, the same treatment as that in the fresh water system cannot be applied. However, if the seawater in the cooling system can be replaced with ozone-containing air intermittently once a week, the adhesion of organisms such as barnacles and mussels to the piping can be prevented without having a bad influence on the other living oceanic organisms.

Keywords:Ozone  Cooling Water Treatment  Biofouling Control  Corrosion  Fresh Water Treatment  Sea Water Treatment