集中式光伏并网输电线路的故障暂态分析与保护
引用本文:李泽文,肖仁平,杜昱东,任申,唐平,颜勋奇.集中式光伏并网输电线路的故障暂态分析与保护[J].电力系统自动化,2019,43(18):120-128.
作者姓名:李泽文  肖仁平  杜昱东  任申  唐平  颜勋奇
作者单位:长沙理工大学电网安全监控技术教育部工程研究中心,湖南省长沙市,410114;国网山东省电力有限公司聊城供电公司,山东省聊城市,252000
基金项目:国家自然科学基金资助项目(51877012)
摘    要:集中式光伏并网输电线路发生故障时,光伏侧的故障暂态过程与系统侧完全不同,导致传统工频量保护动作性能下降。为提高保护动作的可靠性,分析了集中式光伏并网输电线路光伏侧短路电流的故障特征,推导了光伏侧短路电流三个不同阶段的近似解析表达式,并详细分析其功率控制暂态过程的变化特征。发现光伏侧的暂态电流为非旋转量,与系统侧衰减旋转量的波形特征截然不同。基于此特性,提出了一种基于暂态电流波形相关性的纵联保护方法。仿真结果表明所提保护方案在各种故障类型和不同的过渡电阻下均能可靠动作,有望提高光伏并网输电线路的安全运行能力。

关 键 词:输电线路  暂态电流  故障分析  波形相关性  集中式光伏
收稿时间:2018/12/31 0:00:00
修稿时间:2019/7/28 0:00:00

Fault Transient Analysis and Protection for Transmission Lines with Integration of Centralized Photovoltaic
LI Zewen,XIAO Renping,DU Yudong,REN Shen,TANG Ping and YAN Xunqi.Fault Transient Analysis and Protection for Transmission Lines with Integration of Centralized Photovoltaic[J].Automation of Electric Power Systems,2019,43(18):120-128.
Authors:LI Zewen  XIAO Renping  DU Yudong  REN Shen  TANG Ping and YAN Xunqi
Affiliation:Ministry of Engineering Center for Power System Security and Supervisory Control Technology, Changsha University of Science and Technology, Changsha 410114, China,Ministry of Engineering Center for Power System Security and Supervisory Control Technology, Changsha University of Science and Technology, Changsha 410114, China,Liaocheng Power Supply Company of State Grid Shandong Electric Power Co., Ltd., Liaocheng 252000, China,Ministry of Engineering Center for Power System Security and Supervisory Control Technology, Changsha University of Science and Technology, Changsha 410114, China,Ministry of Engineering Center for Power System Security and Supervisory Control Technology, Changsha University of Science and Technology, Changsha 410114, China and Ministry of Engineering Center for Power System Security and Supervisory Control Technology, Changsha University of Science and Technology, Changsha 410114, China
Abstract:When the transmission line with integration of centralized photovoltaic(PV)fails, the fault transient process on PV side is completely different from system side, which leads to a decrease in the performance of the conventional relays based on power frequency. In order to improve the reliability of protection action, the fault characteristics of short-circuit current on PV side for transmission lines with integration of centralized PV are analyzed and then the approximate analytical expressions of short-circuit current on PV side in three different stages are deduced. The variation characteristics of power control transient process are analyzed in detail. It is found that the transient current on PV side is a non-rotational amount, which is completely different from the waveform characteristics of the attenuation rotating amount on system side. Based on the characteristics, a novel polit protection method based on the waveform correlation of transient current is proposed. Finally, the simulation results show that the proposed protection scheme could operate reliably with various fault types and different transition resistances, which is expected to improve the safe operation capability of transmission lines with integration of centralized PV.
Keywords:transmission line  transient current  fault analysis  waveform correlation  centralized photovoltaic