首页 | 本学科首页   官方微博 | 高级检索  
     

检测故障分量的光纤纵联差动保护
引用本文:王晓宇 伍叶凯 黄少锋. 检测故障分量的光纤纵联差动保护[J]. 电力自动化设备, 2004, 24(2): 60-63
作者姓名:王晓宇 伍叶凯 黄少锋
作者单位:华北电力大学,电力工程系,北京,102206;北京四方继保自动化有限公司,北京,100085
摘    要:针对负荷电流对差动保护的影响,对故障分量电流的性质进行了分析,并对基于故障分量向量的电流差动保护动作判据进行了理论分析及EMTP仿真验证,比较得出:故障分量差动判据与传统差动判据相比,在重载线路上发生各种故障,尤其是高阻接地时,能够大大提高差动保护的灵敏度。

关 键 词:电流差动保护  动作判据  故障分量
文章编号:1006-6047(2004)02-0060-04

Optical pilot differential current protection based on fault component
WANG Xiao - yu,WU Ye - kai,HUANG Shao - feng. Optical pilot differential current protection based on fault component[J]. Electric Power Automation Equipment, 2004, 24(2): 60-63
Authors:WANG Xiao - yu  WU Ye - kai  HUANG Shao - feng
Abstract:According to the influence of load on differential protection,the property of fault compo - nent current and the operation criteria for the differential protection based on fault component vector are analyzed and verified with EMTP simulation.The conclusion can be drawn that the ope - ration criteria based on fault component enhance greatly the sensibility of the protection,especially for heavy load lines with high grounding reisistance.
Keywords:differential current protection  operation criteria  fault component  
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《电力自动化设备》浏览原始摘要信息
点击此处可从《电力自动化设备》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号