首页 | 本学科首页   官方微博 | 高级检索  
     

6台主变压器同时跳闸的事故分析及杜绝此类事故的有效措施
引用本文:周国良. 6台主变压器同时跳闸的事故分析及杜绝此类事故的有效措施[J]. 电力设备, 2008, 9(12)
作者姓名:周国良
作者单位:福建省古田溪水力发电厂,福建省古田县,352258
摘    要:某大型水电厂因高压母线TV二次线圈安全接地线被误断开,致使高压中性点未接地的6台主压器的零序过电压保护动作,造成了6台主变压器同时跳闸的重大事故。文章分析了事故原因,并提出了防止此类事故再发生的有效措施。

关 键 词:变压器  TV二次安全接地线  耦合电容  高电压  继电保护

Accident Analysis on Tripping Operation of 6 Main Transformers at the Same Time and Its Effective Measures to Stop This Kind of Accident
ZHOU Guo-liang. Accident Analysis on Tripping Operation of 6 Main Transformers at the Same Time and Its Effective Measures to Stop This Kind of Accident[J]. Electrical Equipment, 2008, 9(12)
Authors:ZHOU Guo-liang
Affiliation:ZHOU Guo-liang(Fujian Gutionxi Hydropower Plant; Gutian 352258; China);
Abstract:The grave accident of tripping operation of 6 main transformers at the same time occurred in a large scale hydropower plant,because of breaking accidentally secondary safe grounding wire of HV bus TV,which caused the miss-operation of zero sequence over-voltage protection in 6 main transformers of without the high voltage neutral grounding.The paper analyzed the accident reason,and put forward the effective measures to prevent this kind of accident occurred again.
Keywords:transformer  secondary safe grounding wire  coupling capacity  high voltage  relay protection  