Experimental study of thermal performance improvement in a cross-flow heat exchanger by using copper foam
Authors:Ahmed M. Hassan  Adil Abbas Alwan  Hameed K. Hamzah
Affiliation:1. Department of Mechanical Engineering, University of Babylon, Hilla, Iraq;2. Department of Medical Industry Engineering, College of Engineering, National University of Science and Technology, Dhi Qar, Iraq
Abstract:In this study, copper foam was used as a porous medium in place of traditional aluminum fins. A comparison between the two heat exchangers—one with fins and the other with copper foam—was conducted under various conditions. The air inlet velocity ranged from 0.9 to 9.3 m/s, and the water inlet temperature ranged from 10°C to 18°C. Different water flow rates were tested. A comparison was made between the performance of copper foam and aluminum fins by calculating several parameters, including thermal resistance, heat exchanger effectiveness, Colburn factor, Nusselt number, friction factor, and area goodness factor (AG). The experimental results showed that at low air velocities, the heat transfer coefficient for both types of heat exchangers was almost equal. However, at high air velocities, the copper foam exhibited a higher heat transfer coefficient. The Colburn factor was higher for the heat exchanger with copper foam than in the conventional fins, where it was equal to 0.1959 for the copper foam and 0.1186 for the fins. On the other hand, the AG was higher in the case of fins than in the heat exchanger with copper foam.
Keywords:area goodness  Colburn factor  copper foam  cross flow  fin  heat exchanger  porous media