Use of C-factor for monitoring of fouling in a shell and tube heat exchanger |
| |
Authors: | Dillip Kumar Mohanty Pravin M Singru |
| |
Affiliation: | a Mechanical Engineering Group, BITS-Pilani Goa Campus, Zuari Nagar, Goa 403726, India |
| |
Abstract: | Heat exchangers operating in process industries are fouled during operations and results in decrease in the thermal efficiency of a heat exchanger. Once the thermal efficiency decreases to a minimum acceptable level, cleaning of the equipment becomes necessary to restore the performance. This paper uses C-factor as a tool for investigation of the performance of a heat exchanger due to fouling which consequently gives information regarding the extent of fouling developed on the heat transfer surfaces. The fouling parameters are predicted by measurements of flow rate and pressure drop. In contrast to most conventional methods, the extent of fouling can be detected considering the flow rate and pressure drop when the heat exchanger operates in transient states. The C-Factor is first calculated through out cleaning period and then compared with the clean and the design value. The results show that the proposed tool is very effective in detecting the fouling developed and the corresponding degradation in heat transfer efficiency of a heat exchanger. Hence the results of this work can find applications in predicting the reduction in heat transfer efficiency due to fouling in heat exchangers that are in operation and assist the exchanger operators to plan cleaning schedules. |
| |
Keywords: | Shell and tube heat exchanger Heat transfer coefficient Pressure drop C-Factor Fouling |
本文献已被 ScienceDirect 等数据库收录! |