首页 | 本学科首页   官方微博 | 高级检索  
     

基于故障模式与后果分析及故障树法的电子式电流互感器可靠性分析
引用本文:王鹏,张贵新,朱小梅,罗承沐,顾立华. 基于故障模式与后果分析及故障树法的电子式电流互感器可靠性分析[J]. 电网技术, 2006, 30(23): 15-20
作者姓名:王鹏  张贵新  朱小梅  罗承沐  顾立华
作者单位:清华大学,电机工程与应用电子技术系,北京市,海淀区,100084;长庆石油勘探局水电厂,水电研究所,甘肃省,庆阳市,712000
摘    要:可靠性分析是电子式互感器研制中的关键环节。在与电磁式电流互感器的可靠性进行对比分析的基础上,分别采用故障模式与后果分析法(failure modes and effects analysis,FMEA)和故障树分析法对一种电子式电流互感器的可靠性进行了研究,建立了完善的FMEA表格和故障树。求取了故障树的所有最小割集,并对该电子式电流互感器的可靠性进行了定性分析。通过电子式电流互感器研制与试验过程中的实例分析,验证了该可靠性分析方法的有效性。

关 键 词:电子式电流互感器  可靠性分析  故障模式与后果分析  故障树分析  最小割集
文章编号:1000-3673(2006)23-0015-06
收稿时间:2006-08-07
修稿时间:2006-08-07

Analysis on Reliability of Electronic Current Transformer Based on Failure Modes, Effects Analysis and Fault Tree Analysis
WANG Peng,ZHANG Gui-xin,ZHU Xiao-mei,LUO Cheng-mu,GU Li-hua. Analysis on Reliability of Electronic Current Transformer Based on Failure Modes, Effects Analysis and Fault Tree Analysis[J]. Power System Technology, 2006, 30(23): 15-20
Authors:WANG Peng  ZHANG Gui-xin  ZHU Xiao-mei  LUO Cheng-mu  GU Li-hua
Affiliation:1. Department of Electrical Engineering, Tsinghua University, Haidian District, Beijing 100084, China;2. Branch of Water and Electric Power Research, Department of Water and Electric Power Supply, Changqing Petroleum Exploration Bureau, Qingyang 712000, Gansu Province, China
Abstract:Reliability analysis is the key procedure during the development of electronic current transformer (ECT). On the basis of the contrastive analysis on reliability of electromagnetic current transformers, by means of failure modes and effects analysis (FMEA) as well as fault tree analysis (FTA) the reliability of a kind of electronic current transformer is researched, and perfect worksheets of both FMEA and FTA are established. All of minimum cut sets of fault trees are found out and the qualitative analysis on the reliability of the ECT is conducted. The effectiveness of the presented reliability analysis method is verified by the results of the analysis on two practical examples during the development and test process of the ECT.
Keywords:electronic current transformer  reliability analysis  failure modes and effects analysis  fault tree analysis  minimum cut sets