首页 | 本学科首页   官方微博 | 高级检索  
     

海拔对导线交流电晕可听噪声影响的电晕笼试验结果与分析
引用本文:唐剑,何金良,刘云鹏,迎建,陈豫朝. 海拔对导线交流电晕可听噪声影响的电晕笼试验结果与分析[J]. 中国电机工程学报, 2010, 0(4)
作者姓名:唐剑  何金良  刘云鹏  迎建  陈豫朝
作者单位:电力系统及发电设备控制和仿真国家重点实验室(清华大学电机系);国网电力科学研究院;
基金项目:“十一五”国家科技支撑计划重大项目(2006BAA02A19,2006BAA02A20,2006BAA02A04); 国家自然科学基金项目(50777035)~~
摘    要:我国高压输电线路面临着高海拔特殊问题,利用可移动式电晕笼系统在4个不同海拔对3种导线进行了交流电晕可听噪声试验研究,得出了可听噪声海拔修正的初步结果。试验结果表明,如果按线性关系修正,得到的海拔修正系数为3.2dB/1000m,与国外3.33dB/1000m的修正系数非常吻合。然而,研究表明,海拔对导线交流可听噪声的影响不是线性的,由海拔较高地区试验数据对比得到的可听噪声海拔修正系数要小于由海拔较低地区对比得到的海拔修正系数;通过分析测试结果得出了粗略的海拔修正系数与海拔的关系。最后,推荐了一种高海拔输电线路可听噪声海拔修正方法,适用范围扩展至海拔3000m以上地区,供今后我国高海拔实际工程参考。

关 键 词:高海拔  输电线路  可听噪声  交流电晕  电晕笼  电晕效应  

Test Results and Analysis of Altitude-change Effect on Audible Noise of AC Corona Occurring on Conductors With Corona-test Cage
TANG Jian,HE Jin-liang,LIU Yun-peng,YANG Ying-jian,CHEN Yu-chao ,Haidian District,Beijing ,China,. State Grid Electric Power Research Institute,Wuhan ,Hubei Province,China). Test Results and Analysis of Altitude-change Effect on Audible Noise of AC Corona Occurring on Conductors With Corona-test Cage[J]. Proceedings of the CSEE, 2010, 0(4)
Authors:TANG Jian  HE Jin-liang  LIU Yun-peng  YANG Ying-jian  CHEN Yu-chao   Haidian District  Beijing   China  . State Grid Electric Power Research Institute  Wuhan   Hubei Province  China)
Affiliation:TANG Jian1,HE Jin-liang1,LIU Yun-peng2,YANG Ying-jian2,CHEN Yu-chao2 (1. State Key Lab of Control , Simulation of Power Systems , Generation Equipments(Dept. of Electrical Engineering,Tsinghua University),Haidian District,Beijing 100084,China,2. State Grid Electric Power Research Institute,Wuhan 430074,Hubei Province,China)
Abstract:High voltage power transmission faces the problem of high altitude in China. In this paper, a mobile corona test cage is firstly applied to measure the AC corona audible noises of three types of transmission bundle lines in four areas with different altitudes. The effect on audible noise from altitudes was analyzed in details. Based on linear correction relation, a correction coefficient of 3.2 dB/1 000 m was obtained which is in good agreement with the foreign coefficient 3.33 dB/1 000 m suggested by forei...
Keywords:high altitude  transmission line  audible noise  AC corona  corona test cage  corona performance  