首页 | 本学科首页   官方微博 | 高级检索  
     

输电线路镀锌铁塔塔脚局部腐蚀失效分析及防护
引用本文:陈彤,庄建煌,黄伟林,谈天,张俊喜.输电线路镀锌铁塔塔脚局部腐蚀失效分析及防护[J].中国电力,2015,48(5):139-143.
作者姓名:陈彤  庄建煌  黄伟林  谈天  张俊喜
作者单位:1. 国网福建省电力有限公司电力科学研究院,福建 福州 350007; 2. 国网福建省电力有限公司莆田供电公司,福建 莆田 351100; 3. 上海电力学院 上海市电力材料防护与新材料重点实验室,上海 200090
基金项目:国家自然科学基金资助项目(51271110);国家电网福建省电力公司科研资助项目(NC2012068)
摘    要:输电杆塔是否牢固关系到输电线路的安全运行。针对输电线路铁塔塔脚局部腐蚀现象,应用电化学试验方法对塔脚特殊环境的腐蚀行为进行模拟试验与腐蚀机理研究。结果表明,塔脚处的特殊结构及环境因素是导致其局部腐蚀失效的主要原因。在此基础上提出了相应的防护措施并在输电线路的铁塔上加以应用,经复查取得了良好的预期效果。

关 键 词:铁塔  塔脚  局部腐蚀  失效分析  防护措施  
收稿时间:2015-02-22

Corrosion Failure Analysis and Protection for Tower Foot of Hot Galvanized Transmission Tower
CHEN Tong,ZHUANG Jianhuang,HUANG Weilin,TAN Tian,ZHANG Junxi.Corrosion Failure Analysis and Protection for Tower Foot of Hot Galvanized Transmission Tower[J].Electric Power,2015,48(5):139-143.
Authors:CHEN Tong  ZHUANG Jianhuang  HUANG Weilin  TAN Tian  ZHANG Junxi
Affiliation:1. Electric Power Research Institute of Fujian Electric Power Co. Ltd., Fuzhou 350007, China; 2. Putian Electric Power Supply Bureau of Fujian Electric Power Co., Ltd., Putian 351100, China; 3. Shanghai Key Laboratory of Materials Protection and Advanced Materials in Electric Power, Shanghai University of Electric Power, Shanghai 200090, China
Abstract:The fastness of transmission tower is very important to transmission line operation safety. The simulation test for tower foot corrosion under special environment is performed; and the corrosion mechanism is investigated by using electrochemical measurement. Results show that the corrosion is caused by the dust cover which exposed to environment rich in water and oxygen. The protection measure is proposed based on the corrosion mechanism and applied in transmission line tower. The re-test shows the proposed protection measure has anticipated effect.
Keywords:transmission tower  tower foot  corrosion  failure analysis  protection measure  
点击此处可从《中国电力》浏览原始摘要信息
点击此处可从《中国电力》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏