凤南线500 kV电抗器内部放电故障的诊断 |
| |
引用本文: | 王瑞珍,胡惠然,邓万婷.凤南线500 kV电抗器内部放电故障的诊断[J].湖北电力,2001,25(2):47-48. |
| |
作者姓名: | 王瑞珍 胡惠然 邓万婷 |
| |
作者单位: | 湖北省电力试验研究院, |
| |
摘 要: | 介绍了500kV电抗器在系统调试过程中内部放电故障的诊断,分析了故障产生的原因,说明了油中气体分析与电气试验相结合是综合判断充油电气设备内部故障最有效的方法。
|
关 键 词: | 电抗器 调试 内部放电 故障诊断 输变电工程 |
文章编号: | 1006-3986(2001)02-0047-02 |
修稿时间: | 2000年12月18 |
Diagnosis on the Internal Discharge Fault Occurred in a 500 kV Reactor of Fengnan Transmission Project |
| |
Abstract: | A diagnostic method for a internal discharge fault occurred in a 500 kV reactor during system commissioning was introduced and the causes were analyzed as well.It was demonstrsted that gas analysis combined with electrical test is a most effective means for fault diagnosis. |
| |
Keywords: | kV reactor commissioning discharge fsult diagnosis |
本文献已被 CNKI 维普 万方数据 等数据库收录! |