联网后海南电网与主网严重故障下的相互影响及解列措施研究
引用本文:张勇,陈建斌,余畅,柳勇军,胡剑琛,赵勇.联网后海南电网与主网严重故障下的相互影响及解列措施研究[J].南方电网技术,2009,3(5):50-53.
作者姓名:张勇  陈建斌  余畅  柳勇军  胡剑琛  赵勇
作者单位:1. 南方电网电力调度通信中心,广州,510623
2. 南方电网技术研究中心,广州,510623
3. 海南电网公司,海口,570203
摘    要:对南方电网主网和海南电网严重故障情况下的相互影响进行了研究,结论为:主网严重故障可能造成海南电网频率升高、降低,甚至功角失稳;而海南电网的严重故障对主网则影响较小,一般不会导致主网功角失稳。建议在港城侧与福山侧分别配置综合解列装置,实现高、低频解列和失步解列功能。

关 键 词:海南电网  南方电网  联网  相互影响  解列
收稿时间:8/3/2009 12:00:00 AM

Study on Interactions between Hainan Power Grid and China Southern Power Grid and Seperation Measures after Interconnection under Severe Faults
ZHANG Yong,CHEN Jianbin,YU Chang,LIU Yongjun,HU Jianchen and ZHAO Yong.Study on Interactions between Hainan Power Grid and China Southern Power Grid and Seperation Measures after Interconnection under Severe Faults[J].Southern Power System Technology,2009,3(5):50-53.
Authors:ZHANG Yong  CHEN Jianbin  YU Chang  LIU Yongjun  HU Jianchen and ZHAO Yong
Affiliation:CSG Dispatching and Communication Certer, Guangzhou 510623, China;;CSG Technology Research Center, Guangzhou 510623,;CSG Dispatching and Communication Certer, Guangzhou 510623, China;;CSG Technology Research Center, Guangzhou 510623,;Hainan Power Grid, Haikou 570203, China;CSG Technology Research Center, Guangzhou 510623,
Abstract:The interaction of Hainan Power Grid HPG and China Southern Power Grid CSG under severe faults after their interconnection is analyzed, and it is concluded that the severe faults occurred in CSG may cause frequency raise or depression of HPG, and even out-of-step while the severe faults in HPG has less influence on CSG, generally not enough to cause out-of-step of CSG. It is proposed to install seperation devices at Gangcheng and Fushan sides with the functions of high or low frequency or out-of-step tripping.
Keywords:Hainan Power Grid  China Southern Power Grid  interconnection  interaction  seperation