Investigation of volatile organic compounds in office buildings in Bangkok,Thailand: Concentrations,sources, and occupant symptoms
Authors:Maneerat Ongwandee  Rathakheth Moonrinta  Sirima Panyametheekul  Chalongkwan Tangbanluekal  Glenn Morrison
Affiliation:1. Faculty of Engineering, Mahasarakham University, Mahasarakham, Thailand;2. Department of Environmental Engineering, Chulalongkorn University, Bangkok, Thailand;3. Department of Pathology, Mahidol University, Bangkok, Thailand;4. Department of Civil, Architectural, and Environmental Engineering, Missouri University of Science and Technology, MO, USA
Abstract:To conserve energy, office buildings with air-conditioning systems in Thailand are operated with a tight thermal envelope. This leads to low fresh-air ventilation rates and is thought to be partly responsible for the sick building syndrome symptoms reported by occupants. The objectives of this study are to measure concentrations and to determine sources of 13 volatile organic compounds (VOCs) in office buildings with air-conditioning systems in the business area of Bangkok. Indoor and outdoor air samples from 17 buildings were collected on Tenax-TA sorbent tubes and analyzed for individual VOCs by thermal desorption-gas chromatography/mass spectrometry (TD–GC/MS). Building ventilation was measured with a constant injection technique using hexafluorobenzene as a tracer gas. The results show that the VOC concentrations varied significantly among the studied buildings. The two most dominant VOCs were toluene and limonene with average concentrations of 110 and 60.5 μg m−3, respectively. A Wilcoxon sum rank test indicated that the indoor concentrations of aromatic compounds and limonene were statistically higher than outdoor concentrations at the 0.05 level, while the indoor concentrations of chlorinated compounds were not. Indoor emission factors of toluene and limonene were found to be highest with the average values of 80.9 and 18.9 μg m−2 h−1, respectively. Principal component analysis was applied to the emission factors of 13 VOCs, producing three components based on source similarities. Furthermore, a questionnaire survey investigation and field measurements of building air exchange pointed to indoor air complaints related to inadequate ventilation.
Keywords:Volatile organic compound  Emission rate  Office buildings  Principal component analysis  Sick building syndromes
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号