首页 | 本学科首页   官方微博 | 高级检索  
     

SF6/N2—高分子薄膜复合绝缘电击穿特性的试验研究
引用本文:曹滨.SF6/N2—高分子薄膜复合绝缘电击穿特性的试验研究[J].哈尔滨理工大学学报,1998,3(6):60-62.
作者姓名:曹滨
作者单位:哈尔滨理工大学
摘    要:研究了SF6/N2-高分子薄膜构成的复合绝缘电击穿特性。研究结果表明:该种复合绝缘中高分子薄膜的介电常数越小,击穿场强越高,其复合绝缘总击穿电压越高;高分子薄膜间隙加粘合介质以排除气隙,可使复合绝缘总击穿电压提高,所得结果与结论为SF6气体绝缘电气设备的绝缘结构设计提供了参考。

关 键 词:电击穿试验  高分子薄膜  氟化硫  复合绝缘  氮气

Experimental Study on Electric Breakdown Behaviour of SF 6/N 2-Polymer Film Composite Insulation
Cao Bin.Experimental Study on Electric Breakdown Behaviour of SF 6/N 2-Polymer Film Composite Insulation[J].Journal of Harbin University of Science and Technology,1998,3(6):60-62.
Authors:Cao Bin
Abstract:AC electric breakdown behaviour of composite insulation SF 6/N 2-polymer film is studied Experimental results show that AC breakdown voltage on the composite insulation increases with decreasing of the polymer film permittivity and addition of liquid adhesive in the gap of film for elimination of gas These results provide reference for the insulation structure design of electrical apparatus with SF 6/N 2-polymer film composite insulation
Keywords:gaseous insulation  composite dielectrics  electric breakdown
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号