A novel wavelet transform technique for on-line partial discharge measurements. 1. WT de-noising algorithm
Authors:Hao Zhang TR Blackburn BT Phung D Sen
Affiliation:Dept. of Electr. Eng. & Telecommun., New South Wales Univ., NSW;
Abstract:Medium and high voltage power cables are widely used in the electrical industry with substantial growth over the last 20-30 years ago, particular in the use of XLPE insulated systems. Ageing of the cable insulation is becoming an increasing problem that requires development of reliable methods for on-line condition assessment. For insulation condition assessment of MV and HV cables, partial discharge (PD) monitoring is one of the most effective techniques. However on-site and on-line PD measurements are affected by electromagnetic interference (EMI) that makes sensitive PD detection very difficult, if not impossible. This paper describes implementation of wavelet transform techniques to reject noise from on-line partial discharge measurements on cables. A new wavelet threshold determination method is proposed with the technique. With implementation of this novel de-noising method, PD measurement sensitivity has been greatly improved. In addition, a full AC cycle data recovery can be achieved instead of focusing only on recovering individual PD pulses. Other wavelet threshold de-noising methods are discussed and examined under a noisy environment to compare their performance with the new method proposed here. The method described here has been found to be superior to the other wavelet-based methods
Keywords: