孤岛微网并联逆变器环流抑制与母线电压控制
引用本文:张继红,杨建民.孤岛微网并联逆变器环流抑制与母线电压控制[J].电测与仪表,2021,58(2):125-132.
作者姓名:张继红  杨建民
作者单位:内蒙古科技大学信息工程学院,内蒙古包头014010;内蒙古科技大学信息工程学院,内蒙古包头014010
基金项目:内蒙古自治区关键技术攻关项目
摘    要:针对孤岛微网中采用传统下垂控制的并联微源逆变器之间存在较大环流及母线电压和频率偏移问题,文中从环流的一般性定义出发,分析了环流与负荷功率分配之间的定量关系,在此基础上将环流抑制问题转化为功率精确分配问题,并提出了一种母线电压和频率自恢复的改进鲁棒下垂控制方法.将PI控制器引入无功电压控制环中,实现无功功率的精确分配并加...

关 键 词:并联逆变器  环流抑制  功率分配  母线电压控制  鲁棒下垂
收稿时间:2019/4/30 0:00:00
修稿时间:2019/4/30 0:00:00

Circulating current restraining and bus voltage control of parallel inverters in islanding microgrid
Zhang Jihong and Yang Jianmin.Circulating current restraining and bus voltage control of parallel inverters in islanding microgrid[J].Electrical Measurement & Instrumentation,2021,58(2):125-132.
Authors:Zhang Jihong and Yang Jianmin
Affiliation:School of Information Engineering,Inner Mongolia University of Science and Technology,School of Information Engineering,Inner Mongolia University of Science and Technology
Abstract:Aiming at the problems of large circulating current and bus voltage and frequency deviation in islanding microgrid parallel micro-source inverters system with traditional droop control, the quantitative relation between circulating current and load power sharing was analyzed according to the general definition of circulating current, on this basis, the problem of circulating current restraining was transformed into the problem of accurate power sharing, and an improved robust droop control method with bus voltage and frequency self-recovery function was proposed. The PI controller was introduced into the reactive power-voltage control loop to realize the accurate reactive power sharing and accelerate its dynamic sharing process, which can restrain the steady-state circulating current and improve the dynamic current sharing performance. The bus voltage and frequency closed-loop control was adopted to track its rated value and enhance bus voltage quality. In view of the new problem of power sharing disproportion after other inverters paralleling, the corresponding solution was proposed. The PSCAD/EMTDC cases simulation results show the correctness and validity of the proposed scheme.
Keywords:parallel inverters  circulating current restraining  power sharing  bus voltage control  robust droop