On the maximum smoke temperature under the ceiling in tunnel fires
Authors:LH Hu  R Huo  W Peng  WK Chow  RX Yang
Affiliation:

aState Key Laboratory of Fire Science, University of Science and Technology of China, Hefei, Anhui, China

bDepartment of Building Services Engineering, Areas of Strength: Fire Safety Engineering, Research Centre for Fire Engineering, The Hong Kong Polytechnic University, Hong Kong, China

cYunnan General Fire Brigade, Kunming, Yunnan, China

Abstract:Maximum smoke temperature under the ceiling in a tunnel fire was studied experimentally and numerically. Full-scale burning tests in two vehicular tunnels of length 3.27 and 1.032 km with and without operating the longitudinal ventilation system were carried out. Smoke temperatures at selected positions under the ceiling were measured under different longitudinal ventilation velocities. Two different pool fires of 1.6 and 3 MW were set up. Computational Fluid Dynamics (CFD) simulations with Fire Dynamics Simulator (FDS) version 3.10 were carried out on those scenarios. CFD predicted smoke temperatures were firstly verified by comparing with the measured values at those selected positions, and then compared with the calculated values using the empirical equation due to Kurioka et al. Fairly good agreement was achieved, though the slope of the tunnel was not considered in this empirical equation.
Keywords:Maximum smoke temperature  Tunnel fire  Longitudinal ventilation velocity  Full-scale tests  CFD simulation  FDS