小电流接地故障暂态过程的LC谐振机理
引用本文:薛永端,薛文君,李娟,徐丙垠.小电流接地故障暂态过程的LC谐振机理[J].电力系统自动化,2016,40(24):137-145.
作者姓名:薛永端  薛文君  李娟  徐丙垠
作者单位:中国石油大学(华东)信息与控制工程学院, 山东省青岛市 266580,中国石油大学(华东)信息与控制工程学院, 山东省青岛市 266580,电网智能化调度与控制教育部重点实验室(山东大学), 山东省济南市250061,山东理工大学智能电网研究中心, 山东省淄博市 255049
基金项目:国家自然科学基金资助项目(51477184);国家高技术研究发展计划(863计划)资助项目(2012AA050212)
摘    要:对于小电流接地故障,传统基于健全相充电与故障相放电的暂态机理,尚未得到严格理论或实践验证,且仅能反映部分暂态过程。提出一种基于电感—电容(LC)谐振的小电流接地故障暂态机理,即在建立基于线路分布参数小电流接地故障全网模型的基础上,分析各模网络及同模网络内不同检测点阻抗的依频变化(交替呈现容性与感性)特性,给出其间发生LC串联/并联谐振的条件与能量交换规律。研究发现,小电流接地故障暂态过程由同模网络内单条出线、不同线路间的若干组LC并联/串联谐振以及线模和零模网络间LC串联谐振组成,其中频率最小且能量最大的模网络间串联谐振为主谐振,其产生的暂态电压电流含有明确的故障位置信息且易于利用。

关 键 词:小电流接地系统  单相接地故障  暂态  谐振机理
收稿时间:2015/12/9 0:00:00
修稿时间:2016/11/20 0:00:00

LC Resonance Mechanism of Transient Process of Earth Fault in Non-solidly Earthed Network
XUE Yongduan,XUE Wenjun,LI Juan and XU Bingyin.LC Resonance Mechanism of Transient Process of Earth Fault in Non-solidly Earthed Network[J].Automation of Electric Power Systems,2016,40(24):137-145.
Authors:XUE Yongduan  XUE Wenjun  LI Juan and XU Bingyin
Affiliation:College of Information and Control Engineering, China University of Petroleum(East China), Qingdao 266580, China,College of Information and Control Engineering, China University of Petroleum(East China), Qingdao 266580, China,Key Laboratory of Power System Intelligent Dispatch and Control(Shandong University), Ministry of Education, Jinan 250061, China and Research Center for Smart Grid, Shandong University of Technology, Zibo 255049, China
Abstract:Traditional transient mechanism based on the charging and discharging of distributed capacitance to earth for single-phase earth faults in non-solidly earthed networks has not yet been analyzed and validated strictly in theory or field. The traditional mechanism only partly reflects the resonance of transient processes and therefore is not accurate or comprehensive enough. A transient mechanism based on LC resonance for single-phase earth fault in non-solidly earthed networks is proposed. Based on the established single-phase earth fault model using distribution line parameters, the impedance characteristics of the frequency-dependency between different modes and different lines in the same mode(the impedance characteristic will alternately appear to be capacitive and inductive)are analyzed. The LC series/parallel resonance conditions and the energy exchange law between capacitive lines and inductive lines are given. A study has found that the transient process of single-phase earth fault can be produced by LC series or parallel resonance in single line, different lines in the same mode, as well as LC series resonance between different modes. The transient current produced by the main resonance(smallest resonance frequency in all the LC series/parallel resonance)contains clear fault location information.
Keywords:non-solidly earthed network  single-phase earth fault  transient  resonance mechanism