首页 | 本学科首页   官方微博 | 高级检索  
     

线路绝缘子直流污闪电压修正研究
引用本文:张福增,杨皓麟,赵锋,王黎明,关志成,周军,李武峰,文华,马仪.线路绝缘子直流污闪电压修正研究[J].高电压技术,2008,34(3):451-455.
作者姓名:张福增  杨皓麟  赵锋  王黎明  关志成  周军  李武峰  文华  马仪
作者单位:1. 清华大学深圳研究生院,深圳,518055
2. 中国电力科学研究院,北京,100085
3. 云南电力试验研究院,昆明,650031
摘    要:为了给出线路绝缘子不同污秽分布条件下直流污闪电压线性海拔修正系数,便于在海拔≤2 km地区直流线路外绝缘的设计,实验研究了在实际海拔1 970 m条件下绝缘子电弧的发展特性。研究表明:绝缘子上下表面污秽分布情况对瓷绝缘子直流电弧发展路径影响较大,造成直流污闪电压随海拔升高下降的程度不同。通过比较不同海拔高度下(0与2 km)210 kN钟罩型绝缘子人工污秽试验结果,提出了绝缘子上下表面污秽分布均匀与不均匀两种条件下直流污闪电压线性海拔修正系数分别为6%和3%,并利用大吨位(300 kN)钟罩型绝缘子试验结果验证了该线性修正系数。结果表明,该修正系数也适用于大吨位绝缘子。

关 键 词:瓷绝缘子  直流  污闪电压  海拔修正  电弧  高海拔
文章编号:1003-6520(2008)03-0451-04
修稿时间:2007年5月25日

Investigation on Altitude Correction Factor of Flashover Voltage of Porcelain Insulator for DC Transmission Lines
ZHANG Fu-zeng,YANG Hao-lin,ZHAO Feng,WANG Li-ming,GUAN Zhi-cheng,ZHOU Jun,LI Wu-feng,WEN Hua,MA Yi.Investigation on Altitude Correction Factor of Flashover Voltage of Porcelain Insulator for DC Transmission Lines[J].High Voltage Engineering,2008,34(3):451-455.
Authors:ZHANG Fu-zeng  YANG Hao-lin  ZHAO Feng  WANG Li-ming  GUAN Zhi-cheng  ZHOU Jun  LI Wu-feng  WEN Hua  MA Yi
Affiliation:1.Graduate School in Shenzhen,Tsinghua University,Shenzhen 518055,China;2.China Electric Power Research Institute,Beijing 100085,China;3.Yunnan Electric Power Test and Research Institute(Group) Co.,Ltd.,Kunming 650031,China)
Abstract:In order to put forward the linear correction factor under different contamination distribution condition,this paper presents the results of study on the contamination characteristics of porcelain insulators under uniform and non-uniform contamination distribution conditions in high altitude areas.The arcing behavior on natural polluted insulator surfaces was studied using a PCI-2000S high speed camera.Experimental results indicated that under uniform contamination,DC arcs levitated more easily from the porcelain surfaces,which led to a low utilization ratio of the insulator leakage distance,and made flashover voltage become very low.With non-uniform contamination,the arcs propagated along the insulator surface making full use of the leakage distance,resulting in a higher flashover voltage than with uniform contamination.Consequently,the effect of altitudes on flashover voltage differed greatly in the two different conditions.Flashover characteristics of 210kN anti-fog insulators were investigated with uniform and non-uniform conditions at different altitudes.Two different linear altitudes correction factors of flashover voltages for different contamination conditions were deduced by comparing the experimental results of 210kN anti-fog insulators at different altitudes.In addition,flashover characteristics of 300kN anti-fog insulator were also studied at different altitudes.Test results for 300kN anti-fog insulator indicate that the linear relationship is in good agreement with 300kN anti-fog insulator.Therefore,these correction factors can be used in outdoor insulation design for DC transmission projects.
Keywords:porcelain insulator  DC  flashover voltage  altitude correction  arc  high altitude
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏