首页 | 本学科首页   官方微博 | 高级检索  
     

填料-高压微雾复合式两级直接蒸发冷却空调机组的研制
引用本文:李成成,黄翔,汪超,吴生,屈元,霍海红,沈柏青,刘晓峰,陈本林,康健.填料-高压微雾复合式两级直接蒸发冷却空调机组的研制[J].制冷与空调(北京),2011(3):116-120.
作者姓名:李成成  黄翔  汪超  吴生  屈元  霍海红  沈柏青  刘晓峰  陈本林  康健
作者单位:[1]西安工程大学 [2]南通昆仑空调有限公司
摘    要:介绍核电站常规岛用两级直接蒸发冷却空调机组的优点、工作原理及设计过程,并对实验样机进行测试。实验数据表明,在南通中湿度地区,当室外空气的干湿球温差为4~5℃时,该组合式空调机组对室内空气降4~5℃,使之接近室外空气的湿球温度。指出两级直接蒸发冷却空调机组在核电站常规岛中具有广泛的应用前景。

关 键 词:两级直接蒸发冷却  空调机组  常规岛  滴水式填料空气冷却器  高压微雾

Development of two-stage direct evaporative cooling air-conditioning units combined with filler and high pressure micro fog
Li Chengcheng Huang Xiang Wang Chao Wu Sheng Qu Yuan Huo HaihongShen Boqing Liu Xiaofeng Chen Benlin Kang Jian.Development of two-stage direct evaporative cooling air-conditioning units combined with filler and high pressure micro fog[J].Refrigeration and Air-conditioning,2011(3):116-120.
Authors:Li Chengcheng Huang Xiang Wang Chao Wu Sheng Qu Yuan Huo HaihongShen Boqing Liu Xiaofeng Chen Benlin Kang Jian
Affiliation:Li Chengcheng) Huang Xiang) Wang Chao) Wu Sheng) Qu Yuan) Huo Haihong)Shen Boqing) Liu Xiaofeng) Chen Benlin) Kang Jian) )(Xi'an Polytechnic University) 2)(Nantong Kunlun Air-Conditioning Co.,Ltd.)
Abstract:Describes the advantages,working principle and design process of two-stage direct evaporative cooling air-conditioning units applied into conventional island nuclear power plant and tests the experiment prototype.The experimental data show that the temperature difference is 4~5 ℃ between dry and wet bulb of outdoor air at Nantong,air-conditioning units can make indoor air decrease 4~5 ℃ and make it close to wet bulb temperature of the outdoor air.Points out that two direct evaporative cooling air-conditioning unit has a wide application prospect in conventional island nuclear power plant.
Keywords:two-stage direct evaporative cooling  air-conditioning unit  conventional island  air coolers with filler-dripping  high-pressure micro fog
本文献已被 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号