首页 | 本学科首页   官方微博 | 高级检索  
     


Analytical Method for Coordination of Surge Arresters with Current-Limiting Fuses
Authors:Harder   John E. Hughes   Albert E. Vosicky   Jan
Affiliation:Distribution Apparatus Division, Westinghouse Electric Corporation, P. O. Box 341, Bloomington, IN 47402.;
Abstract:Many industrial power systems have lightning exposure, requiring surge (lightning) arresters; dry-type transformers, requiring low protective levels; and high available fault currents, making the use of current-limiting fuses desirable. On occasion, current-limiting fuse arc voltages have resulted in destruction of low characteristic arresters. A traditional guideline has been to select arrester types and ratings that will not spark over on current limiting fuse maximum arc voltage?an approach that may not be entirely viable for industrial systems. A step-by-step analytical approach to the selection of surge arresters for use with current-limiting fuses is presented. The method presumes arrester sparkover and is based on determination of system energy, fuse arc voltage and arrester back voltage characteristics, and arrester energy capability.
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号