首页 | 本学科首页   官方微博 | 高级检索  
     


Experimental evaluation of adaptive three-tank level control
Authors:Cartes David  Wu Lei
Affiliation:FAMU-FSU College of Engineering, Department of Mechanical Engineering, Florida State University, Tallahassee, Florida 32310, USA.
Abstract:Liquid level control through regulation of mass flow rates is an important application in various areas of the power industry. Very often a PID controller is used for these applications. This paper compares a nonconventional PID controller and three different types of adaptive controller, a direct model reference adaptive controller (MRAC), an indirect MRAC with Lyapunov estimation, and an indirect MRAC with recursive least-squares (RLS) updating estimation, for liquid level control. By implementing all four controllers on a three-tank system, the performances of each are compared. All controllers track a sinusoidal input very well and overall exhibit somewhat varying performance. The direct MRAC and the indirect MRAC with RLS estimation give the best performance. With Lyapunov estimation and RLS estimation, all the system parameter estimates converge to the reference model values. However, RLS estimation has a much faster convergence. It is concluded that adaptive liquid level control is an improvement over traditional liquid level control when precise level control in three coupled tanks is desired.
Keywords:Adaptive control   Liquid level control   Direct MRAC   Indirect MRAC
本文献已被 ScienceDirect PubMed 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号