基于综合Hausdorff距离的小电流接地故障选线
引用本文:朱振东,邢惠民,刘代,许加利,公茂法,毛永杰.基于综合Hausdorff距离的小电流接地故障选线[J].电测与仪表,2019,56(6):56-62.
作者姓名:朱振东  邢惠民  刘代  许加利  公茂法  毛永杰
作者单位:山东科技大学 电气与自动化工程学院,山东青岛,266510;国网山东省电力公司东营供电公司,山东东营,257091;东营方大电力规划有限公司,山东东营,257091
摘    要:将Hausdorff距离引入小电流接地系统故障选线,利用故障后暂态零序电流波形的相似性度作为故障选线判据,提出改进后的综合Hausdorff距离算法计算暂态零序电流的波形相似度,进行故障线路筛选。采用MATLAB/SIMULINK软件对不同故障条件分别进行仿真。实验结果表明,综合Hausdorff距离算法不受接地电阻、故障电压初相角、短路距离以及电网结构等因素的影响,具有准确性高,抗噪声能力强,检测速度快和对采样频率限制低的优点。

关 键 词:小电流接地系统  故障选线  暂态零序电流  波形相似性度  综合Hausdorff距离
收稿时间:2018/7/9 0:00:00
修稿时间:2018/7/9 0:00:00

Fault Line Selection in Small Current Grounding System based on Compositive Hausdorff Distance
ZHU Zhendong,Xing Huimin,LIU Dai,XU Jiali,GONG Maofa and Mao Yongjie.Fault Line Selection in Small Current Grounding System based on Compositive Hausdorff Distance[J].Electrical Measurement & Instrumentation,2019,56(6):56-62.
Authors:ZHU Zhendong  Xing Huimin  LIU Dai  XU Jiali  GONG Maofa and Mao Yongjie
Affiliation:College of Electrical and Automation Engineering, Shandong University of Science and Technology,State Grid Shandong Electric Power Company Dongying Power Supply Company,State Grid Shandong Electric Power Company Dongying Power Supply Company,Dongying Fangda Electric Power Planning Co.,Ltd., Dongying,College of Electrical and Automation Engineering, Shandong University of Science and Technology,Dongying Fangda Electric Power Planning Co.,Ltd., Dongying
Abstract:Hausdorff Distance is introduced into Fault line selection in a small current grounding system. To solve the problem of fault line selection, this paper proposes an improved Compositive Hausdorff Distance, which uses similarity measurement based on transient zero-sequence currents signals as criteria, to calculate waveform similarity of transient zero-sequence currents. By using MATLAB/SIMULINK software to simulate different fault conditions, the results show that Compositive Hausdorff Distance has the advantages of high accuracy,strong noise immunity, fast detection speed and low limit of sampling frequency, which are not affected by grounding resistance, fault voltage initial angle, short circuit distance and power grid structure.
Keywords:small current grounding system  fault line selection  transient zero sequence current  waveform similarity  Compositive Hausdorff Distance