Experimental investigation of maldistribution in vertical plate falling film tower
Authors:Ritunesh Kumar  Digvijay Patil  Fu Xiao  Piyush Aras
Affiliation:1. Mechanical Engineering Department, Indian Institute of Technology Indore, Madhya Pradesh, India;2. Department of Building Services Engineering, The Hong Kong Polytechnic University, Kowloon, Hong Kong;3. Mechanical Engineering Department, Indian Institute of Technology Kharagpur, West Bengal, India
Abstract:Falling film towers are popular in process industries due to moderate air side pressure drop, less energy ingesting liquid distribution and easy cleanup features. Two major limitations of falling film towers are the uneven distribution of liquid across solid surfaces (maldistribution) and contraction of falling liquid film on the solid surface (poor wetting). Maldistribution of liquid is primarily dependent on the type of liquid distributor and scope of liquid flow (slit opening) across solid surfaces. In the current communication; the influence of liquid distributor on maldistribution problem for vertical plate falling film tower has been experimentally investigated. Four types of liquid distributors: plain tube, spray nozzle, perforated plate, and branch tube distributor have been tested. Effect of parameters: slit opening, liquid flow rate, and the number of plates on maldistribution are also explored. It is found that branch tube distributor is best suited for vertical plate falling film tower application.
Keywords:Branch tube  flow maldistribution  liquid distributors  maldistribution factor  perforated plate  plain tube  slit opening  spray nozzle  vertical falling film tower