Abstract: | The advancement of power electronics technologies has significantly developed the power system stabilizing controllers. Quantitative as well as qualitative evaluation of their effectiveness in power systems is a matter of great importance for the feasibility investigation of these apparatus. In this paper, the possible control region of FACTS controllers with series and/or shunt configuration in a single machine to infinite bus system is formulated in the powerangle curve with a set of algebraic equations. The effectiveness of TCPST (Thyristor‐Controlled Phase Shifting Transformer), SSSC (Static Synchronous Series Compensator), and TCSC (Thyristor‐Controlled Series Compensator) for the improvement of the transient stability is evaluated quantitatively as a numerical example. The correctness of the proposed method has been confirmed by analysis based on the electromagnetic transients simulation with a detailed system model. © 2001 Scripta Technica, Electr Eng Jpn, 138(3): 43–51, 2002 |