摘    要:由于10kV高压开关柜长期温升超标而加速了柜内设备绝缘的老化,导致柜内10kV真空断路器绝缘拉杆性能下降而发生单相弧光接地,而柜内10kV三相限压保护器又由于选型不当而在暂时过电压作用下发生爆炸,引起相间短路,进而扩大了事故范围。

关 键 词:开关柜温升  绝缘拉杆  三相限压器

Analysis of 10kV high -voltage switchgear burnout accident
Wang Shuai.Analysis of 10kV high -voltage switchgear burnout accident[J].Guizhou Electric Power Technology,2011(10):29-31.
Authors:Wang Shuai
Affiliation:Wang Shuai ( Tongren Power Supply Bureau, Tongren 554300 Guizhou, China)
Abstract:Due to the long- term temperature rise in 10kV high -voltage switchgear, it accelerates the aging of devices insulation in switchgear and causes 10kV vacuum circuit breaker insulation pull rod properties degradation. Then the single - phase arc grounding fault occurs. Due to improper selection, under the action of transient overvoltage, the three phase voltage limiter explodes, which causes interphase short circuit, and then extends range.