首页 | 本学科首页   官方微博 | 高级检索  
     


Breakdown characteristics of gas‐insulated switchgear for nonstandard lightning impulse waveforms under nonuniform electric field
Authors:Genyo Ueta  Shuhei Kaneko  Shigemitsu Okabe
Affiliation:Tokyo Electric Power Co., Japan
Abstract:To improve the insulation specification of gas‐insulated switchgear (GIS), it is necessary to recognize the insulation characteristics of SF6 gas during actual surges (called nonstandard lightning impulse waveforms) occurring at field substations. The authors observed the insulation characteristics of SF6 gas gap under various types of nonstandard lightning impulse waveforms and compared them quantitatively with those obtained with standard lightning impulse waveforms. The experimental results were used to derive an evaluation method for real surges, which was applied to typical surges for various UHV and 500‐kV systems. In the preceding study, therefore, only the case of a quasi‐uniform electric field (with a typical range of field utilization factors in the bus of a GIS) was investigated. In the present investigation, the insulation characteristics of an SF6 gas gap for a nonuniform electric field were observed experimentally and an evaluation method for converting nonstandard lightning impulse waveforms equivalently to the standard lightning impulse waveform was investigated. © 2011 Wiley Periodicals, Inc. Electr Eng Jpn, 177(1): 11–18, 2011; Published online in Wiley Online Library ( wileyonlinelibrary.com ). DOI 10.1002/eej.21144
Keywords:gas‐insulated switchgear  nonstandard lightning impulse waveform  insulation characteristics  nonuniform electric field  evaluation method
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号