首页 | 本学科首页   官方微博 | 高级检索  
     


Investigation of a hybrid system of nocturnal radiative cooling and direct evaporative cooling
Authors:Ghassem Heidarinejad  Moien Farmahini Farahani  Shahram Delfani
Affiliation:1. Department of Mechanical Engineering, Tarbiat Modares University, PO Box 14115-143, Tehran 14117, Iran;2. Building and Housing Research Center (BHRC), PO Box 13145-1696, Tehran, Iran
Abstract:In this paper, the results of a study on a hybrid system of nocturnal radiative cooling, cooling coil, and direct evaporative cooling in Tehran have been discussed. During a night, the nocturnal radiative cooling provides required chilled water for a cooling coil unit. The cold water is stored in a storage tank. During eight working hours of the next day, hot outdoor air is pre-cooled by means of the cooling coil unit and then it enters a direct evaporative cooling unit. In this period, temperature variation of the conditioned air is investigated. This hybrid system complements direct evaporative cooling as if it consumes low energy to provide cold water and is able to fulfill the comfort condition whereas direct evaporative alone is not able to provide summer comfort condition. The results obtained demonstrate that overall effectiveness of hybrid system is more than 100%. Thus, this environmentally clean and energy efficient system can be considered as an alternative to the mechanical vapor compression systems.
Keywords:Nocturnal radiative cooling  Cooling coil  Direct evaporative cooling  Hybrid cooling system