Passive mixing control for innovative air diffusion terminal devices for buildings
Authors:Amina Meslem  Ilinca Nastase  Francis Allard
Affiliation:1. LEPTIAB, University of La Rochelle, Pôle Sciences et Technologie, Avenue Michel Crépeau, 17042 La Rochelle, France;2. Technical University of Civil Engineering in Bucharest, Building Services Department, 66 Avenue Pache Protopopescu, 020396 Bucharest, Romania
Abstract:This paper presents an innovative concept for optimized air diffusion in buildings. The method uses passive control of air jet through lobed diffusers. An analysis is done experimentally at different scales for a lobed shaped geometry. A cross-shaped jet is characterized first through an isolated orifice and then at the scale of one perforated panel. An intermediary analysis of two coalescent and a row of cross-shaped jets is also proposed. All the results lead to the same conclusion. The lobed diffuser favors the self-induction compared to a reference conventional circular perforated diffuser. The air flow induced in the case of the lobed perforated panel is in average twice as the one of the circular perforated panel. Despite the consequent gain in air induction for the lobed perforated panel flow, the streamwise maximum velocities display comparable values in the far field which signifies comparable throws for the two flows. Consequently, the presented lobed perforated panel concept can be generalized to different type of diffusers to improve mixing ventilation in buildings.
Keywords:Lobed jets  Twin jets  Mixing  HVAC  Innovative device