DCS信号电缆的屏蔽接地探讨
引用本文:陈钦,杨权,舒茂龙. DCS信号电缆的屏蔽接地探讨[J]. 自动化技术与应用, 2010, 29(12): 110-112
作者姓名:陈钦  杨权  舒茂龙
作者单位:浙江国华浙能发电有限公司,浙江宁海315612
摘    要:某电厂机组调试间发生一次六大风机振动信号全部瞬间跳变导致六大风机跳闸引起机组MFT,经检查是由于风机振动控制拒的接地不合理引起,处理好接地后振动信号正常后未发生跳变情况,文章分析了产生干扰信号的原因及抑制方法。

关 键 词:信号电缆  屏蔽  接地

Research on the Shielding Grounding of the DCS Signal Cable
CHEN Qin,YANG Quan,SHU Mao-long. Research on the Shielding Grounding of the DCS Signal Cable[J]. Techniques of Automation and Applications, 2010, 29(12): 110-112
Authors:CHEN Qin  YANG Quan  SHU Mao-long
Affiliation:( Zhejiang Guohua Zheneng Power Generation Co., Ltd., Ninghai 315612 China )
Abstract:One power plant unit MFT happened because of six-fan vibration signals a moment jump. The trip is due to the unreasonable grounding of the fan vibration control cabinet. Vibration signal is normal after handling the grounding. This article analyzes the reasons of the signal disturbing and its suppression method.
Keywords:signal cable  shielding  grounding