首页 | 本学科首页   官方微博 | 高级检索  
     


An integrated model for the design of air-cooled chiller plants for commercial buildings
Authors:Raymond KL Chan  Eric WM LeeRichard KK Yuen
Affiliation:Department of Building and Construction, City University of Hong Kong, Tat Chee Avenue, Kowloon Tong, Hong Kong
Abstract:Cooling load calculation is the first step in designing the air-conditioning system of a building. The calculated cooling capacity with appropriate buffer is then used to select the number and size of chillers in the system. N + 1 is a common formula used by designers to size the chiller plants in Hong Kong buildings, where N is the actual number of chillers required and 1 is a redundant chiller provided to ensure reliability. This paper reviews the problem of excess capacity and discusses the risk exposure of chiller systems without redundant chillers. The cooling load profiles of the chiller plants of four medium-sized commercial buildings in Hong Kong are reviewed. The risk exposure of chiller systems without redundant chillers can be minimized by applying risk-based preventive maintenance. The just-in-demand design reduces capital cost of the building and frees up funds for continuous energy measurement and improving the energy efficiency of chiller plant systems. This paper presents a model for designing chiller plants that improves the energy efficiency of the plant in a cost effective and thoughtful manner. It is designed with consideration of the life cycle of the plant and real-time continuous commissioning, monitoring, measurement, comparison and execution for better energy management.
Keywords:Air-cooled screw chillers  Commercial buildings  Chiller plant sizing  Energy audit  Redundancy  Reliability
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号