首页 | 本学科首页   官方微博 | 高级检索  
     

变电站直流系统安全隐患的排查和处理
引用本文:邓明燕.变电站直流系统安全隐患的排查和处理[J].四川电力技术,2011,34(5):77-79.
作者姓名:邓明燕
作者单位:四川电力送变电建设公司,四川成都,610051
摘    要:遂宁500 kV变电站投运前两段220 V直流系统母线电压一直处于波动状态,直接影响到遂宁变电站的投运,通过现场排查发现导致直流系统母线电压循环波动原因:6台直流母线绝缘监测装置轮值分时工作循环投入和退出平衡桥公共接地点造成.改进措施:退出绝缘监测装置不平衡桥和轮值分时工作模式,永久投入平衡桥和公共接地点,有效解决了直...

关 键 词:220  V直流系统  母线电压波动  安全隐患  现场排查  改进措施

Investigation and Treatment of Security Risks in Substation DC System
Deng Mingyan.Investigation and Treatment of Security Risks in Substation DC System[J].Sichuan Electric Power Technology,2011,34(5):77-79.
Authors:Deng Mingyan
Affiliation:Deng Mingyan
Abstract:The two segments of bus voltage of 220 V DC system are always in a situation of fluctuation in Suining 500 kV Substation,which directly impacts on the substation being put into operation.Through the on-site investigation,the reasons led to the cyclical fluctuations of bus voltage of DC system are found,that is,the rotating time division mode of 6 sets of DC bus insulation monitoring device has been put into use repeatedly and the common grounding point of the balance bridge has been exited.The improvement a...
Keywords:220 V DC system  bus voltage fluctuation  security risk  site investigation  improvement action  
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号