首页 | 本学科首页   官方微博 | 高级检索  
     


Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement
Affiliation:1. School of Energy and Safety Engineering, Tianjin Chengjian University, Tianjin 300384, China;2. School of Energy and Environment, City University of Hong Kong, Hong Kong, China
Abstract:This work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a.
Keywords:Refrigeration  R450A  R134a  Mixture  Energy efficiency  Drop-in  Réfrigération  R450A  R134a  Mélange de frigorigènes  Efficacité énergétique  Frigorigène de remplacement immédiat