Automation of the temperature elevation test in transformers with insulating oil
Authors:Vicente José Manuel Esteves  Rezek Angelo José Junqueira  de Almeida Antonio Tadeu Lyrio  Guimarães Carlos Alberto Mohallem
Affiliation:UNIFEI/ISEE-Federal University of Itajubá, P.O Box: 50, 37500-903 Itajubá, MG, Brazil. manuel@unifei.edu.br
Abstract:The automation of the temperature elevation test is outlined here for both the oil temperature elevation and the determination of the winding temperature elevation. While automating this test it is necessary to use four thermometers, one three-phase wattmeter, a motorized voltage variator and a Kelvin bridge to measure the resistance. All the equipments must communicate with a microcomputer, which will have the test program implemented. The system to be outlined here was initially implemented in the laboratory and, due to the good results achieved, is already in use in some transformer manufacturing plants.
Keywords:Transformers   Automated tests   Temperature elevation