首页 | 本学科首页   官方微博 | 高级检索  
     

一起500kV变压器绝缘油含氢量超标的原因分析
引用本文:章恩科,王学锦,蔡建辉,黄锐,赵意合.一起500kV变压器绝缘油含氢量超标的原因分析[J].高压电器,2011,47(5):83-86,91.
作者姓名:章恩科  王学锦  蔡建辉  黄锐  赵意合
作者单位:1. 浙江省电力建设有限公司,宁波,315010
2. 温州电力局,温州,325000
摘    要:针对某电厂3台500 kV单相变压器投运前绝缘油中均出现含氢量超标现象,依据绝缘油中产生特征气体的机理和试验数据,展开判断、分析,结果表明其为变压器部件表面吸附的氢释放引起氢含量超标.

关 键 词:变压器  绝缘油  含氢量

Analysis on the Excess Hydrogen Content of Insulating Oil in 500 kV Transformer
ZHANG En-ke,WANG Xue-jin,CAI Jian-hui,HUANG Rui,ZHAO Yi-he.Analysis on the Excess Hydrogen Content of Insulating Oil in 500 kV Transformer[J].High Voltage Apparatus,2011,47(5):83-86,91.
Authors:ZHANG En-ke  WANG Xue-jin  CAI Jian-hui  HUANG Rui  ZHAO Yi-he
Abstract:Aimed at three 500 kV single-phase transformer's insulating oil all appear the excess hydrogen content before operation,based on characteristics of insulating oil gas produced in the mechanism and test data,the estimate and analysis are carried out.It is shown that the excess hydrogen content caused by the release of hydrogen adsorbed on the transformer components surface.
Keywords:transformer  insulating oil  hydrogen content
本文献已被 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号