首页 | 本学科首页   官方微博 | 高级检索  
     

35kV并抗操作过电压故障实例分析
引用本文:金百荣,李电,蔡重凯,陈晓宇,吕丹.35kV并抗操作过电压故障实例分析[J].电力电容器与无功补偿,2016(5).
作者姓名:金百荣  李电  蔡重凯  陈晓宇  吕丹
作者单位:国网绍兴供电公司,浙江 绍兴,312000
摘    要:针对近年来频发的35 kV并抗开断过电压故障,对多起故障实例进行了汇总调查,对故障现象及规律进行了分析,对故障原因及机理进行了仿真解析,对过电压治理措施进行了研究验证。调查发现35 kV并抗开断操作过电压极为严重,空母线开断并抗母线侧存在显著风险,采用断路器并抗中性点侧投切可有效治理35 kV并抗操作过电压。

关 键 词:并联电抗器  真空断路器  操作过电压  空母线  故障

Fault Analysis on Switching Overvoltage of 35 kV Shunt Reactor
Abstract:Aiming at the frequent faults of 35 kV shunt reactor in interrupting overvoltage in recent years, the few cases of faults are collected and investigated,and the fault phenomena and regularity is analyzed, the failure causes and mechanism is simulated and overvoltage control measures are studied and verified. It is found in the investigation that the switching overvoltage of 35 kV shunt reactor is very serious, remarkable risk is existed at the shunt reactor busbar side when switching no load busbar,and adoption of circuit breaker switching at the side of neutral point of shunt reactor can control the switching overvoltage very well.
Keywords:shunt reactor  vacuum circuit breaker  switching overvoltage  no-load busbar  fault
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号