水电机组一次调频与AGC典型控制策略的工程分析及优化
引用本文:何常胜,董鸿魁,翟鹏,苏杭,王新乐,丁永胜. 水电机组一次调频与AGC典型控制策略的工程分析及优化[J]. 电力系统自动化, 2015, 39(3): 146-151
作者姓名:何常胜  董鸿魁  翟鹏  苏杭  王新乐  丁永胜
作者单位:1. 云南电网电力研究院,云南省昆明市,650217
2. 西安热工研究院有限公司,陕西省西安市,710032
基金项目:云南电网公司科技项目(K-YN2012-436)。
摘    要:分析了云南省内已投运水电机组一次调频与自动发电控制(AGC)的典型控制策略,通过工程试验及数据分析,逐一指出其特点及不足。提出功率控制模式下机组采用斜坡函数作为AGC负荷指令,及采用比例—积分—微分(PID)变参数控制分别满足AGC负荷调节和一次调频响应的不同要求;开度控制模式下机组一次调频动作方向与AGC负荷指令方向相反时应屏蔽AGC负荷指令,以及AGC负荷指令首先响应时,应短暂屏蔽一次调频功能等策略。优化了一次调频与AGC间的逻辑关系,并对文中的典型控制策略给出了合理的可行性建议,为水电机组一次调频与AGC寻找更理想的配合策略提供了参考依据。

关 键 词:水电机组  一次调频  自动发电控制  监控系统  调速器
收稿时间:2014-02-08
修稿时间:2014-09-13

Engineering Analysis and Optimization on Typical Control Strategy of Primary Frequency Modulation and Automatic Generation Control of Hydropower Units
HE Changsheng,DONG Hongkui,ZHAI Peng,SU Hang,WANG Xinle and DING Yongsheng. Engineering Analysis and Optimization on Typical Control Strategy of Primary Frequency Modulation and Automatic Generation Control of Hydropower Units[J]. Automation of Electric Power Systems, 2015, 39(3): 146-151
Authors:HE Changsheng  DONG Hongkui  ZHAI Peng  SU Hang  WANG Xinle  DING Yongsheng
Abstract:An analysis is made of the typical control strategy of primary frequency modulation and automatic generation control (AGC) for the operating hydropower units in Yunnan Province. The characteristics and disadvantages of the typical control strategy are pointed out through engineering test and data model analysis. It is proposed that the ramp function is used as AGC commands, and variable parameters control is adopted to meet different requirements of AGC and primary frequency modulation in the power control mode. AGC commands should be shielded when the load instruction of primary frequency modulation and AGC commands are opposite in direction, and the primary frequency modulation function should be shielded momentarily when AGC commands respond first in the gate open control mode. The logical relationship between AGC and primary frequency is optimized, and rational feasibility suggestions are made for the typical control strategy. The paper provides reference for finding a more ideal coordination strategy for the primary frequency modulation and AGC of hydropower units.
Keywords:hydropower units  primary frequency modulation  automatic generation control (AGC)  monitoring system  governor