引用本文:赵峰,文远高.热泵空调系统能耗的温频法模拟与分析[J].建筑节能,2007,35(6):39-43.
作者姓名:赵峰  文远高
作者单位:武汉科技大学城建学院,武汉,430070
摘    要:以武汉近15年的气象数据为依据,计算出武汉地区以2℃为温频段的全年和一班制温频数据.在此基础上,采用温频法对武汉地区一栋办公建筑采用地下水源热泵系统的全年能耗进行模拟,模拟包括办公楼空调系统全年耗电量.同时与空气源热泵进行比较,地下水源热泵系统较空气源热泵系统夏季节能23.3%,冬季节能19.1%.

关 键 词:热泵  空调  能耗模拟  温频法
文章编号:1673-7237(2007)06-0039-05
修稿时间:2006-12-15

Energy Consumption Simulation and Analysis of Heat Pump Air Conditioning System by BIN Method
ZHAO Feng,WEN Yuan-gao.Energy Consumption Simulation and Analysis of Heat Pump Air Conditioning System by BIN Method[J].Construction Conserves Energy,2007,35(6):39-43.
Authors:ZHAO Feng  WEN Yuan-gao
Affiliation:Wuhan University of Science and Technology, Wuhan 430070, China
Abstract:Based on the weather data of a standard year in Wuhan,which derived from the data of the latest 15 years,the data for the BIN(temperature and humidity frequency) method of annual and 8-hours system were calculated.Then the BIN method was adopted to simulate the annual energy-consumption of groundwater heat pump systems(GWSPS) for an office building in Wuhan.Its annual energy-consumption was obtained and compared with the partner of the air source heat pump systems.The results show that the energy consumption of the former was approximately less 23.3% than that of the latter in summer and 19.1% in winter.
Keywords:heat pump  air conditioning  energy consumption simulation  BIN method